AHU-02 South Wing
Air Handling Unit · Trane M-Series Climate Changer · Rooftop South · Riverside Office Complex
Condition — Last 14 Days
Electrical Demand
15-minute power draw, kW — last 14 days
VibrationStaticDev
15-minute readings, mm/s RMS — last 14 days
Air Temperatures
Supply air vs. outdoor air, °C — last 14 days
Zone CO₂StaticDev
Worst zone, ppm — last 14 days
Nameplate & Ratings
- Asset ID
- AHU-02
- Asset type
- Air Handling Unit
- Manufacturer
- Trane
- Model
- M-Series Climate Changer
- Rated motor
- 7.5 kW
- Rated airflow
- 8,000 CFM
- Served zones
- 2
- Heat-recovery wheel
- Yes
- CHW coil design flow
- 47 GPM
- HW coil design flow
- 36 GPM
- Installed
- Jun 15, 2019
- Last major service
- Nov 20, 2025
Fault History
Supply duct high-static safety tripped. Static at trip: 457 Pa. Filter DP: 259 Pa.
Filter differential pressure exceeded warning threshold (250 Pa). Current: 250 Pa. Service filter bank.
Hot-water valve hunting - coil flow oscillating ~28% around demand at 15-minute period; discharge air temperature unstable (±2.5 C around setpoint). Control loop requires retuning.
Discharge air temperature 4 C below setpoint during cold-snap morning warm-up (OA -9.4 C). Hot-water coil at full flow. Self-recovered as coil load stabilized.
Freeze-stat tripped on morning start during cold snap (OA -13.9 C). Mixed-air temp fell below 4 C limit - OA damper actuator found stuck partially open.
Discharge air temperature 4 C below setpoint during cold-snap morning warm-up (OA -11.4 C). Hot-water coil at full flow. Self-recovered as coil load stabilized.
Discharge air temperature 5.5 C below setpoint during cold-snap morning warm-up (OA -12.1 C). Hot-water coil at full flow. Self-recovered as coil load stabilized.
Discharge air temperature 5.6 C below setpoint during cold-snap morning warm-up (OA -12.4 C). Hot-water coil at full flow. Self-recovered as coil load stabilized.
Service History
Triggered by: F-HIGH-STATIC — High-static trip F-HIGH-STATIC (2026-06-03); filter DP warning active since 2026-05-22
Emergency Saturday call-out following high-static trip. Replaced primary MERV-13 filter bank. Pre-change DP 262 Pa (rated max 250 Pa). Coil inspection clean.
Triggered by: Condition monitoring: energy-wheel sensible effectiveness trending down 70% -> ~56% (action level 62%)
Energy-recovery wheel brush seals replaced and matrix cleaned. Post-service sensible effectiveness restored to ~70% (design).
Triggered by: F-VALVE-HUNT — Hot-water valve hunting alarm F-VALVE-HUNT (2026-02-10)
HW valve PI loop retuned (proportional gain halved, integral time doubled); valve stroke verified smooth 0-100%. Discharge air temperature stable within ±1 C after tuning.
Triggered by: F-FREEZE-STAT — Freeze-stat trip F-FREEZE-STAT (2026-01-21)
Freeze-stat trip callout. OA damper actuator linkage seized partially open in -16 C conditions. Linkage freed, lubricated, actuator stroke re-verified. Freeze-stat reset.