Alarm Insights

Analytics on the alarm history — what recurs, what lingers, what chatters, and what each alarm led to. Live alarm handling stays with the real-time BMS.

Unresolved
1
Oldest active 3.7 days
Most Recurring
4×
F-LOW-DAT · AHU-02
Fleeting Patterns
3
Self-clear ≤ 60 min — nuisance alarms
Chattering Patterns
2
≥ 3 annunciations in one day
Stale Patterns
7
Active > 24 h before clearing
Led to Work Orders
57.1%
8 of 14 alarm types

Alarm TrendStaticDev

Alarm occurrences per week, split by severity tier — a rising bar is an asset asking for attention before it trips

Unresolved the Longest

Fan vibration highAHU-01 North Wingactive 3.7 dayssince Jul 2, 2026Unacknowledged

Most Recurring AlarmsStaticDev

4×Discharge air below setpointAHU-02 South Wing · last Jan 21, 2026, 10:30 a.m.WARNINGChatteringFleeting
3×VFD overcurrent tripAHU-03 Production Hall · last Jun 24, 2026, 2:30 p.m.TRIPChattering
1×Fan vibration highAHU-01 North Wing · last Jul 2, 2026, 6:45 a.m.WARNINGOpenStale
1×Fan vibration criticalAHU-03 Production Hall · last Jun 17, 2026, 6:30 p.m.CRITICALStale
1×Chiller high-pressure tripCH-01 Central Chiller · last Jun 18, 2026, 2:30 p.m.TRIP
1×High duct static tripAHU-02 South Wing · last Jun 3, 2026, 2:15 p.m.TRIPFleeting
1×Freeze-stat tripAHU-02 South Wing · last Jan 21, 2026, 6:45 a.m.TRIP
1×Boiler flame-failure lockoutBLR-02 South Boiler · last Jan 20, 2026, 5:45 a.m.TRIP

Most Affected Assets

8×AHU-02 South Wing5 alarm types0critical2medium6low
5×AHU-03 Production Hall3 alarm types1critical3medium1low
2×AHU-01 North Wing2 alarm types0critical0medium2low
2×CH-01 Central Chiller2 alarm types0critical1medium1low
1×BLR-02 South Boiler1 alarm type0critical1medium0low
1×BLR-01 East Boiler1 alarm type0critical0medium1low

Maintenance Outcomes

Alarms resolved by a work order
VFD overcurrent tripAHU-03 Production HallBearing Replacement · Jun 25, 2026 · $2,850
High duct static tripAHU-02 South WingFilter Change · Jun 6, 2026 · $245
Freeze-stat tripAHU-02 South WingActuator Repair · Jan 21, 2026 · $410
Boiler flame-failure lockoutBLR-02 South BoilerIgniter Replacement · Jan 22, 2026 · $260
Chiller efficiency degradedCH-01 Central ChillerCondenser Cleaning · Jun 19, 2026 · $1,150
Fan vibration highAHU-03 Production HallVibration Analysis · May 5, 2026 · $450
Boiler flue temperature highBLR-01 East BoilerBurner Service · Mar 20, 2026 · $980
Hot-water valve huntingAHU-02 South WingControls Tuning · Feb 13, 2026 · $290
Recurring with no corrective action recorded
Discharge air below setpointAHU-02 South Wing · 4× · avg clear 38 minCleared on its own each time — worth a root-cause look or an alarm-limit review before it recurs.

Alarm AnalysisStaticDev

AlarmAssetSeverityCountAvg ClearPatternTakeaway
F-VIB-HIGHFan vibration highAHU-01WARNING1×last Jul 2, 2026, 6:45 a.m.—OpenStaleStill open at the end of the data — active for 3.7 days (since Jul 2, 2026), not yet acknowledged. Needs follow-up.
F-VIB-CRITFan vibration criticalAHU-03CRITICAL1×last Jun 17, 2026, 6:30 p.m.7.5 daysStaleRemained active 7.5 days before clearing — review response and escalation time.
F-OVERCURRENTVFD overcurrent tripAHU-03TRIP3×last Jun 24, 2026, 2:30 p.m.5.8 hChatteringResolved by Bearing Replacement on Jun 25, 2026. Annunciated 3× in a single day — the condition was oscillating at its limit; address the root cause rather than re-acknowledging.
F-HP-TRIPChiller high-pressure tripCH-01TRIP1×last Jun 18, 2026, 2:30 p.m.1.5 hCleared in 1.5 h without a linked work order.
F-HIGH-STATICHigh duct static tripAHU-02TRIP1×last Jun 3, 2026, 2:15 p.m.60 minFleetingResolved by Filter Change on Jun 6, 2026. Self-cleared in ~60 min on average — nuisance-alarm pattern; consider an alarm delay or a revised limit.
F-FREEZE-STATFreeze-stat tripAHU-02TRIP1×last Jan 21, 2026, 6:45 a.m.3 hResolved by Actuator Repair on Jan 21, 2026.
F-FLAME-FAILBoiler flame-failure lockoutBLR-02TRIP1×last Jan 20, 2026, 5:45 a.m.75 minResolved by Igniter Replacement on Jan 22, 2026.
F-COP-LOWChiller efficiency degradedCH-01WARNING1×last Jun 10, 2026, 1:00 p.m.8.8 daysStaleResolved by Condenser Cleaning on Jun 19, 2026. Remained active 8.8 days before clearing — review response and escalation time.
F-FILTER-DIRTYFilter service requiredAHU-02WARNING1×last May 21, 2026, 4:45 p.m.15.7 daysStaleRemained active 15.7 days before clearing — review response and escalation time.
F-VIB-HIGHFan vibration highAHU-03WARNING1×last May 1, 2026, 11:30 a.m.54.8 daysStaleResolved by Vibration Analysis on May 5, 2026. Remained active 54.8 days before clearing — review response and escalation time.
F-FLUE-TEMPBoiler flue temperature highBLR-01WARNING1×last Mar 12, 2026, 9:15 a.m.7.9 daysStaleResolved by Burner Service on Mar 20, 2026. Remained active 7.9 days before clearing — review response and escalation time.
F-VALVE-HUNTHot-water valve huntingAHU-02WARNING1×last Feb 10, 2026, 9:00 a.m.3.3 daysStaleResolved by Controls Tuning on Feb 13, 2026. Remained active 3.3 days before clearing — review response and escalation time.
F-LOW-DATDischarge air below setpointAHU-02WARNING4×last Jan 21, 2026, 10:30 a.m.38 minChatteringFleetingAnnunciated 3× in a single day — the condition was oscillating at its limit; address the root cause rather than re-acknowledging. Self-cleared in ~38 min on average — nuisance-alarm pattern; consider an alarm delay or a revised limit.
F-LOW-DATDischarge air below setpointAHU-01WARNING1×last Jan 21, 2026, 7:30 a.m.60 minFleetingSelf-cleared in ~60 min on average — nuisance-alarm pattern; consider an alarm delay or a revised limit.
Occurrence Log — 19 alarm events in the window
Description
Jul 2, 2026, 6:45 a.m.AHU-01F-VIB-HIGHWARNINGSupply fan vibration crossed warning threshold (5.0 mm/s). Reading: 5.06 mm/s. Rapid onset over ~10 days suggests belt wear or sheave misalignment - inspect drive assembly.———
Jun 24, 2026, 2:30 p.m.AHU-03F-OVERCURRENTTRIPVFD overcurrent protection tripped (trip 3 of the day). Current at trip: 18.5 A. Vibration: 7.29 mm/s. Third trip - unit held out of service pending bearing replacement.Jun 24, 2026, 2:40 p.m.Jun 25, 2026, 7:00 a.m.16.5
Jun 24, 2026, 12:45 p.m.AHU-03F-OVERCURRENTTRIPVFD overcurrent protection tripped (trip 2 of the day). Current at trip: 17.7 A. Vibration: 7.23 mm/s. Second trip after reset. Vibration severely elevated.Jun 24, 2026, 12:55 p.m.Jun 24, 2026, 1:15 p.m.0.5
Jun 24, 2026, 11:00 a.m.AHU-03F-OVERCURRENTTRIPVFD overcurrent protection tripped (trip 1 of the day). Current at trip: 16.2 A. Vibration: 7.21 mm/s. Operator reset after inspection; no obstruction found.Jun 24, 2026, 11:10 a.m.Jun 24, 2026, 11:30 a.m.0.5
Jun 18, 2026, 2:30 p.m.CH-01F-HP-TRIPTRIPHigh discharge-pressure safety trip at peak heat-wave load (OA 34.7 C). Fouled condenser could not reject heat at full load. Unit locked out pending inspection.Jun 18, 2026, 2:50 p.m.Jun 18, 2026, 4:00 p.m.1.5
Jun 17, 2026, 6:30 p.m.AHU-03F-VIB-CRITCRITICALSupply fan vibration crossed critical threshold (7.0 mm/s). Reading: 7.01 mm/s. Schedule immediate maintenance.Jun 17, 2026, 7:30 p.m.Jun 25, 2026, 7:00 a.m.180.5
Jun 10, 2026, 1:00 p.m.CH-01F-COP-LOWWARNINGChiller efficiency degraded: COP trending ~4.1 against ~5.2 expected at this condition. Condenser approach temperature elevated - coil fouling suspected. Schedule condenser cleaning.Jun 10, 2026, 5:00 p.m.Jun 19, 2026, 8:00 a.m.211
Jun 3, 2026, 2:15 p.m.AHU-02F-HIGH-STATICTRIPSupply duct high-static safety tripped. Static at trip: 457 Pa. Filter DP: 259 Pa.Jun 3, 2026, 2:35 p.m.Jun 3, 2026, 3:15 p.m.1
May 21, 2026, 4:45 p.m.AHU-02F-FILTER-DIRTYWARNINGFilter differential pressure exceeded warning threshold (250 Pa). Current: 250 Pa. Service filter bank.May 21, 2026, 6:45 p.m.Jun 6, 2026, 9:00 a.m.376.3
May 1, 2026, 11:30 a.m.AHU-03F-VIB-HIGHWARNINGSupply fan vibration crossed warning threshold (5.0 mm/s). Reading: 5.01 mm/s. Recommend bearing inspection.May 1, 2026, 5:30 p.m.Jun 25, 2026, 7:00 a.m.1,315.5
Mar 12, 2026, 9:15 a.m.BLR-01F-FLUE-TEMPWARNINGFlue-gas temperature elevated (~99 C vs ~70 C expected at this load) and combustion efficiency trending down ~6.7 points - heat-exchanger scaling suspected. Schedule burner service and descale.Mar 12, 2026, 12:15 p.m.Mar 20, 2026, 8:00 a.m.190.8
Feb 10, 2026, 9:00 a.m.AHU-02F-VALVE-HUNTWARNINGHot-water valve hunting - coil flow oscillating ~28% around demand at 15-minute period; discharge air temperature unstable (±2.5 C around setpoint). Control loop requires retuning.Feb 10, 2026, 11:00 a.m.Feb 13, 2026, 4:00 p.m.79
Page 1 of 2