CH-01 Central Chiller
Chiller · Carrier 30XV Air-Cooled Screw Chiller · Central Plant B1 · Downtown Windsor Tower
Condition — Last 14 Days
Electrical Demand
15-minute power draw, kW — last 14 days
VibrationStaticDev
15-minute readings, mm/s RMS — last 14 days
Nameplate & Ratings
- Asset ID
- CH-01
- Asset type
- Chiller
- Manufacturer
- Carrier
- Model
- 30XV Air-Cooled Screw Chiller
- Rated motor
- 68 kW
- Rated airflow
- 0 CFM
- Served zones
- 0
- Heat-recovery wheel
- No
- CHW coil design flow
- 240 GPM
- HW coil design flow
- 0 GPM
- Installed
- May 28, 2020
- Last major service
- Apr 21, 2026
Fault History
High discharge-pressure safety trip at peak heat-wave load (OA 34.7 C). Fouled condenser could not reject heat at full load. Unit locked out pending inspection.
Chiller efficiency degraded: COP trending ~4.1 against ~5.2 expected at this condition. Condenser approach temperature elevated - coil fouling suspected. Schedule condenser cleaning.
Service History
Triggered by: F-COP-LOW — Analytics: COP trending 20%+ below expected; F-COP-LOW warning and heat-wave high-pressure trip F-HP-TRIP
Condenser coils chemically cleaned and rinsed; approach temperature restored to design. COP back to ~5.2 at part load.
Triggered by: Scheduled spring chiller start-up (calendar)
Spring start-up: refrigerant charge verified, oil analysis clean, safeties tested.