Energy Consumption

Electrical energy across monitored assets, with demand profile and heat-recovery offset.

Electrical Energy Consumed
29,795kWh
Avg Daily
993.2kWh/day
Peak Demand
103.3kW
Highest 15-min interval
Energy Cost
$4,455
Open Utility Cost report
Heat Recovered
16,291kWh
29.1× the 561 kWh the wheels consumed

Daily Electrical Energy by Asset

kWh per day, all equipment — click a legend entry to add or remove an asset

Demand Profile by Hour — Air Handling Units

Mean electrical demand (kW) at each hour of day

Demand Profile by Hour — Chillers

Mean electrical demand (kW) at each hour of day

Demand Profile by Hour — Boilers

Mean electrical demand (kW) at each hour of day

Heat-Recovery Contribution

Thermal energy reclaimed by the energy-recovery wheels, kWh per day — energy the coils did not have to supply

Heat-Recovery Wheel Efficiency — Consumption vs. SavingsStaticDev

AssetThermal energy recoveredWheel motor consumedNet benefitReturn ratioAvg effectiveness
AHU-012,965 kWh103 kWh2,862 kWh28.66×73%
AHU-022,982 kWh105 kWh2,877 kWh28.40×73%
AHU-034,430 kWh152 kWh4,278 kWh29.15×72.9%
AHU-043,697 kWh124 kWh3,573 kWh29.79×73%
AHU-052,217 kWh76 kWh2,141 kWh29.17×73.1%

Every kWh of wheel-motor input returns the ratio shown as recovered thermal energy the coils did not have to supply — the wheels pay for themselves many times over while sealed and driven correctly.

Monthly Summary by Asset

2026-06AHU-01738$109.9452372,394
2026-06AHU-02739$109.9752372,412
2026-06AHU-031,212$180.828.92313,585
2026-06AHU-04883$131.575.92372,985
2026-06AHU-05542$80.573.72371,793
2026-06BLR-0172$7.870.100
2026-06BLR-0272$7.870.100
2026-06CH-0112,015$1,804.66103.32360
2026-06CH-028,569$1,285.91612370
2026-07AHU-01138$20.624.743571
2026-07AHU-02138$20.664.643570
2026-07AHU-03201$30.136.843845
Page 1 of 2