BLR-01 East Boiler
Boiler · Viessmann Vitocrossal 300 Condensing Boiler · Boiler Room · East Windsor Business Park
Condition — Last 14 Days
Energy
40kWh
0 run-hours
Alarms
0
None unresolved
Electrical Demand
15-minute power draw, kW — last 14 days
Nameplate & Ratings
- Asset ID
- BLR-01
- Asset type
- Boiler
- Manufacturer
- Viessmann
- Model
- Vitocrossal 300 Condensing Boiler
- Rated motor
- 2.2 kW
- Rated airflow
- 0 CFM
- Served zones
- 0
- Heat-recovery wheel
- No
- CHW coil design flow
- 0 GPM
- HW coil design flow
- 180 GPM
- Installed
- Sep 30, 2019
- Last major service
- Mar 20, 2026
Fault History
F-FLUE-TEMPWARNING
Mar 12, 2026, 9:15 a.m. · cleared Mar 20, 2026, 8:00 a.m.
Flue-gas temperature elevated (~99 C vs ~70 C expected at this load) and combustion efficiency trending down ~6.7 points - heat-exchanger scaling suspected. Schedule burner service and descale.
Service History
BURNER SERVICE$980.00
CorrectiveMar 20, 2026, 8:00 a.m. · K. Dominguez · 300 min downtime
Triggered by: F-FLUE-TEMP — Flue-gas temperature warning F-FLUE-TEMP (2026-03-12); combustion efficiency trending 94% -> ~86%
Heat exchanger descaled, burner tuned and combustion analyzed. Efficiency restored to ~94%; flue temperature back to design.