BLR-02 South Boiler

Boiler · Cleaver-Brooks ClearFire-CE Condensing Boiler · Plant Room A · South Windsor Distribution Centre

Condition — Last 14 Days

Energy
40kWh
0 run-hours
Alarms
0
None unresolved

Electrical Demand

15-minute power draw, kW — last 14 days

Nameplate & Ratings

Asset ID
BLR-02
Asset type
Boiler
Manufacturer
Cleaver-Brooks
Model
ClearFire-CE Condensing Boiler
Rated motor
1.8 kW
Rated airflow
0 CFM
Served zones
0
Heat-recovery wheel
No
CHW coil design flow
0 GPM
HW coil design flow
150 GPM
Installed
Nov 8, 2021
Last major service
Oct 15, 2025

Fault History

F-FLAME-FAILTRIP
Jan 20, 2026, 5:45 a.m. · cleared Jan 20, 2026, 7:00 a.m.

Flame-failure lockout on cold-snap morning start (OA -12.5 C). Three ignition attempts failed; manual reset required. Igniter electrode suspected.

Service History

IGNITER REPLACEMENT$260.00
CorrectiveJan 22, 2026, 10:00 a.m. · K. Dominguez · 90 min downtime

Triggered by: F-FLAME-FAIL — Flame-failure lockout F-FLAME-FAIL (2026-01-20)

Igniter electrode eroded; replaced and gapped. Flame signal strong across three test cycles.