AHU-05 East Campus

Air Handling Unit · York Solution XT AHU · Rooftop Unit 1 · East Windsor Business Park

Condition — Last 14 Days

Peak Vibration
5.7mm/s
Avg while running 4 mm/sStaticDev
Peak Filter ΔP
121Pa
StaticDev
Peak Bearing Temp
56.9°C
StaticDev
Energy
317kWh
138 run-hours
Alarms
0
None unresolved

Electrical Demand

15-minute power draw, kW — last 14 days

VibrationStaticDev

15-minute readings, mm/s RMS — last 14 days

Air Temperatures

Supply air vs. outdoor air, °C — last 14 days

Zone CO₂StaticDev

Worst zone, ppm — last 14 days

Nameplate & Ratings

Asset ID
AHU-05
Asset type
Air Handling Unit
Manufacturer
York
Model
Solution XT AHU
Rated motor
5.5 kW
Rated airflow
6,000 CFM
Served zones
2
Heat-recovery wheel
Yes
CHW coil design flow
35 GPM
HW coil design flow
27 GPM
Installed
Oct 2, 2018
Last major service
Mar 25, 2026

Fault History

No faults recorded.

Service History

PREVENTIVE INSPECTION$300.00
PreventiveMar 25, 2026, 8:30 a.m. · J. Tremblay · 30 min downtime

Triggered by: Scheduled quarterly PM (calendar)

Q1 preventive inspection. Belt retensioned; condensate drain flushed.