AHU-05 East Campus
Air Handling Unit · York Solution XT AHU · Rooftop Unit 1 · East Windsor Business Park
Condition — Last 14 Days
Peak Vibration
5.7mm/s
Avg while running 4 mm/sStaticDev
Peak Filter ΔP
121Pa
StaticDev
Peak Bearing Temp
56.9°C
StaticDev
Energy
317kWh
138 run-hours
Alarms
0
None unresolved
Electrical Demand
15-minute power draw, kW — last 14 days
VibrationStaticDev
15-minute readings, mm/s RMS — last 14 days
Air Temperatures
Supply air vs. outdoor air, °C — last 14 days
Zone CO₂StaticDev
Worst zone, ppm — last 14 days
Nameplate & Ratings
- Asset ID
- AHU-05
- Asset type
- Air Handling Unit
- Manufacturer
- York
- Model
- Solution XT AHU
- Rated motor
- 5.5 kW
- Rated airflow
- 6,000 CFM
- Served zones
- 2
- Heat-recovery wheel
- Yes
- CHW coil design flow
- 35 GPM
- HW coil design flow
- 27 GPM
- Installed
- Oct 2, 2018
- Last major service
- Mar 25, 2026
Fault History
No faults recorded.
Service History
PREVENTIVE INSPECTION$300.00
PreventiveMar 25, 2026, 8:30 a.m. · J. Tremblay · 30 min downtime
Triggered by: Scheduled quarterly PM (calendar)
Q1 preventive inspection. Belt retensioned; condensate drain flushed.